Parameter Setting tool and function block configuration
The operation mode of the function keys and the LEDs must be defined per key and
LED in Parameter Setting tool.
The function key can operate as:
• Pulsed signal
• Each push forces a pulse of a configured time.
• The pulse time can be set in Parameter Setting tool.
• The default pulse time is 200 ms.
• Toggle signal
• Each push changes the state of the signal: OFF-ON-OFF-ON-OFF...
• The default position after power up or reset is OFF.
• Menu shortcut
• When pressing a key configured for that purpose, the function key panel is
hidden and LHMI opens directly in the configured menu.
IEC09000656 V1 EN
Figure 43: LHMI: Function key operation mode
The LEDs have a number of different operation modes, see Figure 44:
• General definitions
• Each LED can illuminate in one of three colors: RED, YELLOW, GREEN.
• Only one color is illuminated at a time.
• The priority for illumination and the color is linked.
Section 6 1MRK 511 261-UUS A
Local HMI engineering
76 650 series ANSI
Engineering Manual