7.5.1 Importing SCD files
Procedure to import a SCD file to PCM600:
1. Select the station in the plant structure.
2. Right-click the station and select Import ...
3. Select the file to be imported from the open standard Windows menu and start the
reading.
4. A SCL Import Options window opens, which queries how the file should be
handled during import, see
Figure 67.
IEC09000631-1-en.vsd
IEC09000631 V1 EN
Figure 67: IEC 61850: Import SCD file
4.1. Click Ignore Substation Section to not import the "SSD-file" part of the SCD-
file.
4.2. Click Don't import IEDs of unknown type to protect the existing IEDs in case
the SCD file does not match the original configuration in PCM600.
4.3. Click Replace unknown ... can be used when it is known, that the file
includes additional IEDs that are needed. The IED of type “Generic IEC
61850 IED” is used to integrate these kinds of IEDs in the plant structure etc.
4.4. Click Ignore PCM Object Type to update the IED object(s) in PCM600 from
the IED type(s) in the SCD file, disregarding if the IED type(s) in the SCD
file matches the IED object(s) in PM600 or not.
4.5. Start Import when the file definition has been completed. A progress
window presents the import procedure.
5. Make connections from sending IEDs to receiving function blocks in SMT.
5.1. Make connections between the signals that the server is sending and all the
GOOSE receive interface function blocks included in the application
configuration on the client’s side.
Section 7 1MRK 511 261-UUS A
IEC 61850 communication engineering
108 650 series ANSI
Engineering Manual