Section 8 IEC 60870-5-103 communication
engineering
8.1 Engineering in PCM600
The Application Configuration tool (ACT) and the Parameter Setting tool (PST) in
PCM600 are used to configure the communication for IEC 60870-5-103 protocol.
1. Add the desired IEC 60870-5-103 function blocks to the application
configuration in the Application Configuration tool.
2. Connect the outputs of desired protection and monitoring function in the
application configuration to the inputs of the corresponding IEC 60870-5-103
function block.
3. Set the function type and desired information number, where an information
number must be supplied, for each IEC 60870-5-103 function block instance in
the Parameter Setting tool.
4. Set the general communication settings for IEC 60870-5-103, available in
function RS485103 or OPTICAL103 depending on choice of serial interface, and
time synchronization parameters in the Parameter Setting tool.
See the Communication protocol manual for IEC 60870-5-103 for more information
about the IEC 60870-5-103 implementation in 650 series.
The COM05 module is equipped with an optical serial and RS485
serial communication interface. IEC60870-5-103 can be communicated
from either of these serial interfaces. The user must select in PST which
interface to use.
8.1.1.1 Selecting to communicate IEC60870-5-103 data via RS485 serial
interface on COM05 module
1MRK 511 261-UUS A Section 8
IEC 60870-5-103 communication engineering
650 series ANSI 113
Engineering Manual